Home
Search:
Manufactures
Acuvim
Crompton
Texmate
Search:
Meter Types
KWH Meters
Revenue Grade
Single Phase
Switchboard
Three Phase
Switchboard
Three Phase
Demand
Watt
Hour Meter
Transformers
Current
Transformers
Potential
Transformers
Switches
Salzer
Switches
Ordering
Information
| |
Acuvim Digital
Power Meter- 3 Phase-TOU Option.
Field configurable multiple parameter display
combinations. Ideal
choice
for replacement of failed analog meters because it mounts
in ANSI 4.5"
or DIN 96mm cut outs.
Modbus communication option.
Ships in 1 day.
Economically
priced $265-380.00.
Place the meter in a DIN or Round cutout.
|
|
Acuvim-CL
may be used as a data gathering device for an intelligent
Power Distribution System or a Plant Automation System. All
monitoring data is available via digital RS485 communication
port running Modbus RTU Protocol.
Power
system quality is important with increasing use of
electronic loads such as computers, ballasts or variable
frequency drives. With the Acuvim-L power analysis option,
any phase current or voltage can be displayed and the
harmonic content calculated.
By knowing the harmonic distribution, action can be taken to
prevent
overheated transformers, motors, capacitors, neutral
wires and
nuisance breaker trips. Redistribution of the system
loading can
also be determined.
Choose the
model number via needed parameters.
Offers
improved monitoring and controlling of power
distribution system. The electric power parameters available
on the ultra-compact Acuvim-L are: True-RMS
measuring parameter, 4-quadrant Energy
Power
Quality Analysis, Clear LCD screen, Bright Back light.
|
|
Meter Prices:
Available
Option include: 1 Amp CT input, Low
voltage DC power supply,
DIN Rail mount w/o display.
Acuvim-AL-5 Amp $265.00 Standard.
Acuvim-AL-1 Amp
$265.00 Optional 1 Amp input.
Acuvim-AL-5 Amp
$295.00
Low
VDC
power supply.
Acuvim-BL-5 Amp $295.00 Digital Pulse, alarm
Output.
Acuvim-CL-5 Amp $325.00 RS485 Communication
port.
Acuvim-CL-5 Amp $280.00 DIN Mount-No Display,
RS485 Communication port.
Acuvim-CL-1 Amp $360.00 RS485 Communication
port.
Acuvim-CL-5 Amp $370.00 RS485 Communication
port 24VDC power supply.
Acuvim-DL-5 Amp
$350.00 RS485 Communication port I/O
Options available.
Acuvim-EL-5 Amp
$380.00 RS485 Communication TOU Measurement.
Acuvim-EL-5 Amp
$330.00 RS485 Comm. No Display TOU Measurement.
Acuvim-KL-5 Amp
$195.00 RS485 Communication port.
Energy/Power meter.
Acuvim L Series Brochure
Acuvim L Manual
Modicon Modbus Map
Acuvim CL, DL, EL, KL, Communication Hookup
Drawings.
|
|
| Function |
Parameter |
AL |
BL |
CL |
DL |
EL |
KL |
| Real Time Measurement |
Phase Voltage |
U1, U2, U3, |
> |
> |
> |
> |
> |
|
| Line Voltage |
U1-2, U2-3, U3-1, |
> |
> |
> |
> |
> |
|
| Current |
I1, I2, I3,LN * |
> |
> |
> |
> |
> |
> |
| Power
(Watts) |
P1, P2, P3, Psum |
> |
> |
> |
> |
> |
> |
| Reactive Power |
Q1, Q2, Q3, Qsum |
> |
> |
> |
> |
> |
> |
| Apparent Power |
S1, S2, S3, Ssum |
> |
> |
> |
> |
> |
> |
| Power factor |
PF1, PF2, PF3, PF |
> |
> |
> |
> |
> |
|
| Load nature |
L ?C ?R |
> |
> |
> |
> |
> |
|
| Frequency |
Hz |
> |
> |
> |
> |
> |
|
| Energy and Demand |
Energy
(Wh's) |
Ep-imp, Ep-exp |
> |
> |
> |
> |
> |
> |
| Reactive Energy |
Eq-imp, Eq-exp |
> |
> |
> |
> |
> |
> |
| Apparent Energy |
Es |
> |
> |
> |
> |
> |
> |
| Current Demand |
Dmd-L1,-L2, -L3 |
> |
> |
> |
> |
> |
|
| Power Demand |
Psum, Qsum, Ssum |
> |
> |
> |
> |
> |
|
| Time of Use |
Energy |
TOU 4 Tariffs, 12 Seasons, 14 Schedules |
|
|
|
|
TOU |
|
| Power Quality |
Voltage Unbalance |
U_unbal |
> |
> |
> |
> |
> |
|
| Current Unbalance |
I_unbal |
> |
> |
> |
> |
> |
|
| Voltage THD |
V1, V2, V3 |
> |
> |
> |
> |
|
|
| Current THD |
I1, I2, I3 |
> |
> |
> |
> |
|
|
| Individual Harmonics |
2nd-15th Voltage,Current** |
> |
> |
> |
> |
|
|
| Statistics |
Max Current Demand |
L1, L2, l3, Max |
> |
> |
> |
> |
> |
|
| Max Power demand |
Psum, Qsum,,Ssum |
> |
> |
> |
> |
> |
|
| Max&Min Voltage |
|
> |
> |
> |
> |
> |
|
| Max&Min Current |
|
> |
> |
> |
> |
> |
|
|
Running Hour |
Hour |
> |
> |
> |
> |
> |
> |
|
Load Running Hour |
Hour |
|
|
|
> |
> |
> |
| I/O |
Energy Pulse Out
Only. No Alarm.
|
2 DO. Configured-pulse out for kWh and kVar, adjustable
rate & width |
|
> |
|
|
|
|
| Alarm Output. |
|
|
> |
|
|
|
|
| Communication |
RS485 Port. |
Modbus RTU |
|
|
> |
> |
> |
> |
| Second RS485 Port. |
Modbus RTU |
|
|
|
*** |
*** |
|
| Extension I/O |
4Digital in,
2 Dig/Out
|
SOE, Pulse counter, Pulse Output, Alarm
Output. |
|
|
|
*** |
*** |
|
| * KL-no neutral measurement |
|
|
|
|
|
|
|
| ** DL Measures Harmonics from 2nd-25th *** Optional |
|
|
|
|
|
Options Input/Output
Power Analysis
BL- Alarm Output
 | One (1) alarm parameter may be set within a specified
time interval. |
 | If indicated parameter is over or under its setting
limit and persists |
 | over the specified time interval, the event will be
recorded with time |
 | stamps and trigger the Alarm DO output. The indicated
parameter can |
 | be selected from any of the 31 parameters available.
|
Pulse Output
 | Two Digital outputs can be configured as pulse output
for kWh and kVarh. |
 | The pulse rate and width can be set. |
CL -Communication
 | RS485, Industry standard Modbus RTU protocol |
|
|
\

|