Home
Manufactures
ConZerv
Crompton
Texmate
Meters
Wilbac Meter
Meter Types
Single Phase
Switchboard
Three Phase
Switchboard
Three Phase
Demand
Watt
Hour Meter
Bargains
Meter
Sensors
Current
Transformers
Potential
Transformers
Salzer
Switches
Temperature
Measurement
Ordering
Information
| |
Switchboard 3-Phase Power Meter.
3-phase amps,
volts, Watt,
displayed simultaneously.
Field configurable multiple parameter display
combinations. Ideal
choice
for replacement of failed analog meters because it mounts
in ANSI 4.5"
or DIN 96mm cut outs.
Modbus communication option.
Ships in a few
days.
Solves so many
monitoring problems with a price range of $320-370.00.
Acuvim-CL may
be used as a data gathering device for an intelligent Power
Distribution System or a Plant Automation System. All
monitoring data is available via digital RS485 communication
port running Modbus RTU Protocol.
Modicon Modbus Map.
Power
system quality is important with increasing use of
electronic loads such as computers, ballasts or variable
frequency drives. With the Acuvim-L power analysis option,
any phase current or voltage can be displayed and the
harmonic content calculated.
By knowing the harmonic distribution, action can be taken to
prevent
overheated transformers, motors, capacitors, neutral
wires and
nuisance breaker trips. Redistribution of the system
loading can
also be determined.
Choose the
model number via needed parameters.
Offers
improved monitoring and controlling of
power distribution system. The electric power parameters
available on the ultra-compact Acuvim-L are: True-RMS measuring parameter, 4-quadrant Energy
Power Quality Analysis, Clear LCD screen,Bright Orange Back light.
Acuvim-AL
$320.00 Standard
Acuvim-BL
$340.00 Digital Relay Output
Acuvim-CL
$370.00 RS485 Modbus Communication
|
|
Function |
Parameter |
AL |
BL |
CL |
|
|
|
|
|
|
|
Phase Voltage |
VL-N, 1, 2, 3 |
V |
V |
V |
| REAL TIME |
Line Voltage |
V L-L, 1-2, 2-3, 3-1 |
V |
V |
V |
| METERING |
Current |
I1, 2, 3,L-N |
V |
V |
V |
|
Power |
P1, 2, 3, sum |
V |
V |
V |
|
Reactive Power |
Q1, 2, 3, sum |
V |
V |
V |
|
Apparent Power |
Ssum |
V |
V |
V |
|
Power Factor |
PF1, PF2, PF3, |
V |
V |
V |
|
Load Nature L/C/R |
L/C/R |
V |
V |
V |
|
|
|
|
|
|
|
ENERGY |
Ep_iimp, p_exp, |
V |
V |
V |
| ENERGY & |
REACTIVE ENERGY |
Eq_imp, q_exp |
V |
V |
V |
| DEMAND |
CURRENT DEMAND |
Dmd_I1,DDmd_I2 md_II3 |
V |
V |
V |
|
POWER DEMAND |
Dmd_Psum, md_QQsum |
V |
V |
V |
|
|
|
|
|
|
|
Voltage Unbalance |
U_unbl |
V |
V |
V |
| POWER |
Current Unbalance |
I_unbl |
V |
V |
V |
| QUALITY |
Voltage THD |
THD_V1, THD_V2, THD_V3, |
V |
V |
V |
|
Current THD |
THD_I1, THD_I2, THD_I3 |
V |
V |
V |
|
Individual Harmonics |
2 nd 15 th (Current/Voltage) |
V |
V |
V |
|
|
|
|
|
|
|
Max Current Demand |
Dmd_I1, I2, I3, max Dmd |
V |
V |
V |
|
Max Power Demand |
Dmd, Psum, Qsum_max |
V |
V |
V |
| STATISTICS |
Max and Min Voltage |
|
V |
V |
V |
|
Max and Min Current |
|
V |
V |
V |
|
|
|
|
|
|
| HOUR |
Running Hour |
Hour |
V |
V |
V |
| I/O |
Energy Pulse Output |
|
|
V |
|
|
Alarm Output |
|
|
V |
|
| COMMUNICATION |
RS-4485 MODBUS ®-RTU Protocol |
|
|
V |
|
|
|
|
|
|
Acuvim-L Standard Features:
- Metering
- Voltage V1, V2, V3, V12, V23, V31
- Current I1, I2, I3, In
- Power P1, P2, P3, Psum
- Reactive Power Q1, Q2, Q3, Qsum
- Apparent Power Ssum
- Frequency F
- Power Factor PF1, PF2, PF3, PF
- Energy Ep_imp, Ep_exp
- Reactive Energy Eq_imp, Eq_exp
- Power Quality
- Voltage Harmonics 2nd to 15th and THD
- Current Harmonics 2nd to 15st and THD
- Voltage Imbalance Factor U_unbl
- Current Imbalance Factor I_unbl
- Max/Min Statistics with Time Stamps
- Running Hour
Options Input/Output Power Analysis
Alarm
 | One (1) alarm parameter may be set within a specified time
interval. |
 | If indicated parameter is over or under its setting limit and
persists |
 | over the specified time interval, the event will be recorded
with time |
 | stamps and trigger the Alarm DO output. The indicated parameter
can |
 | be selected from any of the 31 parameters available. |
Pulse Output option
 | Two Digital outputs can be configured as pulse output for kWh
and kVarh. |
 | The pulse rate and width can be set. |
Communication