Home
Manufactures
ConZerv
Crompton
Texmate
Meters
Wilbac Meter
Meter Types
Single Phase
Switchboard
Three Phase
Switchboard
Three Phase
Demand
Watt
Hour Meter
Bargains
Meter
Sensors
Current
Transformers
Potential
Transformers
Salzer
Switches
Temperature
Measurement
Ordering
Information
| |
Crompton Integra
1530 DIN Style 3-Phase Digital Panel Meter
|
Measurement display and
communicates 23 parameters in a 96x96mm case.
True RMS measurement for accurate
measurement of distorted waveforms Ideal for
retrofitting analog switchboard panel meter
applications Large red LEDs for easy viewing
|

Prices Integra 1530
Configuration
Software
Integra Technical Data |
Crompton Integra 1530 Panel Meter.
Low voltage Switchgear and distribution
Process Control Monitoring Energy
and Building Management Systems Generator sets
Self contained.
Displayed Parameters Screen:
1. User Selectable
2. System voltage, avg. current, total
power
3. Voltage per phase L-N,
4. Voltage per phase to phase
5. Current per phase
6. System neutral current, frequency & PF
7. Power - kW (Active) & VAr (Reactive), kVA (App)
8. kWh (Active energy)
9. kVAr.h (Reactive energy)
10. Demand A & kW
11. Maximum demand A & kW
|
Specification
Input
Voltage:
57.7, 63.5, 69.3, 110, 115,
120, 220, 230, 240, 254, 277V, 346 L/N
100, 110, 120, 208, 380, 400, 415, 440 480V
L/L Measuring Range 10 - 100% Range of use 5 - 120%
Current:
5 amps (Standard) or 1 amp
(Optional) Measuring Range 10 - 100% Range of use 5 - 120%
Maximum C.T. ratio 4000:5A or 4000:1A
Frequency:
45 to 65Hz
Power Factor:
Range of use 0.5 Lag - 1 -
0.8 Lead
Overloads
Voltage:
2 x for 1 second (x10) at
10 second intervals Maximum terminal voltage 1.2 times normal
Current:
20 x for 1 second (x5) at 5
minute intervals Maximum continuous terminal current 1.2 times
|