Home
Manufactures
ConZerv
Crompton
Texmate
Meters
Wilbac Meter
Meter Types
Single Phase
Switchboard
Three Phase
Switchboard
Three Phase
Demand
Watt
Hour Meter
Bargains
Meter
Sensors
Current
Transformers
Potential
Transformers
Salzer
Switches
Temperature
Measurement
Ordering
Information
| |
Crompton Integra 520 Panel Meter DIN Style.
Economical Digital Maximum Demand
Panel Meter Indicator.
|
Measurements of fundamental electrical parameters, integrating high accuracy
measurement technology with the simplicity and visibility of a single display system.
Got Questions, want to place an order? Call us.
|
 |
The Crompton Integra 520 Panel
Meter
Distribution pillars, Feeder
panels & switchboards,
Low voltage
switchgear
Process
control and monitoring,
Motor
control centers
Energy
monitoring,
Maximum Demand measurements.
Prices
Integra 520
Technical Details |
Benefits
Totally new
look MDI, 10
measurements in one unit,
Programmable C.T. ratios
Programmable time period, Readable in
bright sunlight, Replaces 3 combined MDI &
1 Voltmeter
Simple to
use, Measures
down to 2.5% of nominal input, High
overload capability
Features
High
contrast LCD, Large
characters, Standard 96
x 96mm DIN case
Self
powered or Auxiliary powered, Average
sensing, Password
protected
Reset can
be disabled, Two button
operation, Designed to
meet world-wide standard
approvals for safety and performance, EMC and LVD.
Input Specification
System:
Three phase
- three wire, Model 244-523. Three phase - four wire, Model 244-524
Voltage:
100-120V
L-L,190-240V L-L, 380-480V L-L
Current:
5 amps
(Standard) or 1 amp (Optional) Maximum C.T. ratio 8000:5A or 8000:1A
Measuring Range:
Current 2.5 - 120% Current Demand 2.5 - 120% Voltage (Auxiliary Powered)
2.5 - 120% Voltage (Self Powered) 75 - 125% of 115, 230
or 460V
Frequency:
45 to 66Hz
Demand Integration Period:
8, 15, 30 & 60 minutes
Burden:
Voltage:
Each line
0.2VA approx.
Current:
Each phase
0.6VA approx.
Overload Capability:
Continuous:
120% of
nominal (600V Max)
Short Duration:
2 x nominal
for one second
Repeated 10 times at 10 second intervals.
Current:
Continuous:
120% of
nominal
Short Duration:
20 x
nominal/1second Repeated 5 times at 5 minute intervals
10 x
nominal for 3 seconds Repeated 5 times at 5 minute intervals 5 x nominal
for 5seconds Repeated 5 times at 5 minute intervals
Auxiliary Supply
A.C. voltage:
100 - 120V 190 - 240V 380 - 480V -10% of lower nominal +20% of upper nominal
Burden 3VA approx.
Enclosure:
Size:
96 x 96 mm
DIN
Material:
Flame
retardant to UL94V-0/V-2
Terminals:
M3.5
captive screw & clamp
Accuracy Class
Voltage:
+1.5% of
nominal
Current:
+1.5% of
nominal
Current Demand:
3% of
nominal
Climatic
Temperature:
Operating
-10 to +70°C Storage -20 to +80°C Calibration 23°C
Temp Coeff:
±0.013%/°C
(typical)
Humidity:
95% RH non
condensing
Isolation:
2.2kV RMS
50Hz for 1 minute
Surge Voltage
Test:
IEC 801-5
High Frequency Disturbance:
4.2kV peak
IEC 255
Display
High
contrast LCD & Annunciation Characters
10.5mm high 3 lines of
data,
4 digits per line 4 digit
resolution with a floating decimal point for each value
All
parameters available via single button operation cascading through 4 screens
Comprehensive set-up facility via two buttons Update time
7.5 seconds approx. for
A & V, 1/8 of demand integration time for current demand.
|